مشخصات فنی
| Item No. |
VPH888-12.5/3P+1P (T1+T2) |
| SPD according to EN/IEC 61643-11 |
Type1+Type 2 (T1+T2) |
| Network |
IT-TN |
| Application |
L-PE |
| Max. continuous operating voltage Uc |
AC880V, 50Hz/60Hz |
| Impulse current Iimp(10/350μs) |
12.5kA |
| Nominal discharge current In(8/20μs) |
20kA |
| Max. discharge current Imax(8/20µs) |
80kA |
| Voltage protection level Up |
≤3.4kV |
| Internal protective devices |
Built-in thermal tripping device |
| Max. backup fuse |
250A gL/gG |
| Short-circuit withstand capability |
25kArms |
| Response time |
≤25ns |
| Cross-sectional area |
6~35mm² |
| Stripping length terminals |
12.5mm |
| Tightening torque |
3N·m |
| Failure indicator |
The lightning protection module has an indication window, which turns red in the fault state |
| Remote signaling mode |
RSC: Remote signal contact, NC-COM-NO contact |
| Performances of remote signal contact |
AC: 250V/0.5A; DC:250V/0.1A, 125V/0.2A, 75V/0.5A |
| Remote cross-sectional area |
Max. 1.5mm² |
| Installation method |
35mm DIN rail |
| Housing material |
PBT UL94-V0 |
| Protection class |
IP20 |
| Operating temperature |
-40℃~+80℃ |
| Relative humidity |
≤95%(25℃) |
| Operating altitude |
≤3000m |
| Electric clearance required by EN 60664-1:2003 |
≥6mm |
| Outline dimensions(without terminal) |
90mm × 72mm × 77mm |
| Module pluggable |
Pluggable module |
نکته: برای کسب اطلاعات بیشتر، لطفاً به راهنمای کاربری یا صفحه مشخصات محصول در اسناد زیر مراجعه کنید.